1. Question:
For 400-440Hz operation Lambda requires the use of an undervoltage relay. What kind of device is this?
Answer:
Many relay companies have undervoltage relays available (often called UVRs). One example is the Tyco's VCAA.
Set the undervoltage threshold to 85VAC minimum. Ensure current rating of the relay is adequate.